180AYC10B |
Maximum leakage current each Line to Ground:
120 VAC 60Hz 277 VAC 50Hz
16A 62 mA 106 mA
25 & 36A 68 mA 118 mA
63A 74 mA 128 mA
80, 100 & 150A 74 mA 129 mA
180, 200A 111 mA 192 mA
Hipot rating (one minute):
Line to Ground: 1850 VDC
Line to Line: 1850 VDC
Line to Neutral: 1450 VDC
Rated Voltage (max):
Phase to Phase: 480 VAC
Phase to Ground: 277 VAC
Operating Frequency: 50/60 Hz
Rated Current: 16 to 200A
Operating Ambient Temperature Range
(at rated current I
r
): -10°C to +40°C
In an ambient temperature (T
a
) higher than +40°C
the maximum operating current (I
o
) is calculated as
follows: I
o
= I
r
?(85-Ta)/45
AYC Series
108
AYC Series
3-phase WYE RFI Power Line Filters for High Noise Applications
Dimensions are in inches and millimeters unless otherwise speci?ed. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Speci?cations subject to change.
Corcom Product Guide
Catalog: 1654001
Issue Date: 06.2011
For email, phone or live chat, please g |
171.39K |
MACOM[Tyco Electronics] |
|