描述:80
Dimensions are in inches and millimeters unless otherwise speci?ed. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Speci?cations subject to change.
Corcom Product Guide
Catalog: 1654001
Issue Date: 06.2011
For email, phone or live chat, please go to
te.com/help
corcom.com
T Series
T Series
High Performance RFI Power Line Filters for Switching Power Supplies
Maximum leakage current each Line to Ground:
3, 6 & 10A ET Models VT Models
@120 VAC 60 Hz: .30 mA .75 mA
@250 VAC 50 Hz: .50 mA 1.2 mA
15 & 20A
@120 VAC 60 Hz: .30 mA 1.2 mA
@250 VAC 50 Hz: .50 mA 2.0 mA
Hipot rating (one minute):
Line to Ground: 2250 VDC
Line to Line: 1450 VDC
Rated Voltage (max): 250 VAC
Operating Frequency: 50/60 Hz
Rated Current: 3 to 20A
Operating Ambient Temperature Range
(at rated current I
r
): -10°C to +40°C
In an ambient temperature (T
a
) higher than +40°C
the maximum operating current (I
o
) is calculated as
follows: I
o
= I
r
?(85-Ta)/45
? Superior co